Schneider Electric ATV950D18N4EU Variable Speed Drive, 18.5kW (25hp), 380-480V, IP55
Schneider Electric
ATV950D18N4EU
Variable Speed Drive, 18.5kW (25hp), 380-480V, IP55
MPN: ATV950D18N4EU
PPN: SCH-ATV950D18N4EU
UNSPSC: 39122001
Spec sheet
Loading compare button...
If you can't find the product or are unsure which one you need, please use the Product Selector tool below
In Stock
Company Stock:
00
Lead times may vary. For an accurate estimate please contact us.
Loading dialog...
Looking to buy a large quantity?
To view product inventory
Description
Engineered for industrial applications, the Altivar Process ATV900 variable speed drive from Schneider Electric delivers exceptional performance and versatility. With a robust power rating of 18.5 kW (25 hp) and compatibility with both asynchronous and synchronous motors, this drive is designed to operate efficiently within a voltage range of 380 to 480V. Its IP55 rating ensures reliable performance in demanding environments, while features like adjustable acceleration and deceleration ramps, integrated braking chopper, and comprehensive electromagnetic compatibility testing make it a top choice for process control.
The ATV900 series is equipped with advanced safety functions, including Safe Torque Off and Safe Stop 1, ensuring operational safety and compliance with industry standards. With a wide array of communication options, including Modbus TCP and EtherNet/IP, it seamlessly integrates into existing systems for enhanced automation capabilities. This variable speed drive not only optimizes motor control but also contributes to energy savings and reduced emissions, making it a smart investment for sustainable industrial operations.
Specifications
Communications & Management Attributes
Communication Port Protocol
Modbus TCP, Modbus serial, EtherNet/IP
Conformance Attributes
Product Certifications
DNV-GL, TÜV, ABS, ATEX INERIS, UL, Bureau Veritas, CSA
relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC, relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC, relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC, relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC, relay output R1 resistive, cos phi = 1 3 A 250 V AC, relay output R1 resistive, cos phi = 1 3 A 30 V DC, relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC, relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC
Maximum Transient Current
47 A 60 s normal duty), 47.6 A 60 s heavy duty)
Maximum Associated Fuse Rating
63.0 A
Maximum Output Frequency
599 Hz
Minimum Switching Current
relay output R1, R2, R3 5 mA 24 V DC
Maximum Thdi<48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12
Brake Chopper Integratedtrue
Maximum Input Current Per Phase33.4 A
Maximum Output Voltage480.0 V
Important Information Attributes
Product Contributes To Saved And Avoided Emissions
YES_SSI2, Yes
Persona Type Names
End User, Original Equipment Manufacturer, OEM - Control Panelbuilder, System Integrator
Asynchronous Motor Control Profile
optimized torque mode, variable torque standard, constant torque standard
Data Format
8 bits, configurable odd, even or no parity Modbus serial, 8 bits, configurable odd, even or no parity
Electromagnetic Compatibility
electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2, radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3, electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5, conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input, AQ1, AQ2 +/- 0.2 % analog output
Motor Slip Compensation
not available in permanent magnet motor law, can be suppressed, adjustable, automatic whatever the load
Number Of Addresses
1-247, 1-247 Modbus serial
Protection Type
safe torque off drive, motor phase break drive, thermal protection motor, safe torque off motor, motor phase break motor, thermal protection drive, overheating drive, overcurrent between output phases and earth drive, overload of output voltage drive, short-circuit protection drive, overvoltages on the DC bus drive, line supply overvoltage drive, line supply undervoltage drive, line supply phase loss drive, overspeed drive, break on the control circuit drive
Switching Frequency
2...16 kHz adjustable, 4...16 kHz with derating factor
380...480 V 18.5 kW normal duty, 380...480 V 15.0 kW heavy duty
Environmental Class During Operation2
class 3C3 according to IEC 60721-3-3, class 3S3 according to IEC 60721-3-3
Environmental Class During Transport2
class 2C3 according to EN 60721-3-2, class 2S1 according to EN 60721-3-2
Carbon Footprint Of The End Of Life Phase C1 To C4
5.6326465927, 6 kg CO2 eq.
Carbon Footprint Of The Manufacturing Phase A1 To A3
223 kg CO2 eq., 222.6584786054
Environmental Class During Operation3
class 3C3 according to IEC 60721-3-3, class 3S3 according to IEC 60721-3-3
Environmental Class During Transport3
class 2C3 according to EN 60721-3-2, class 2S1 according to EN 60721-3-2
Local Data Status
Publishable
Device Type
Variable speed drive - VSD Compacts
Traceability
Yes
Average Life Duration
10 year(s)
Scope Perimeter
At least in Europe
End Of Life Doc Ref
ENVEOLI1406001EN
Reach Full Compliance Status Id
CONTAINS_SVHC
ROHS EUR In Scope
No
ROHS EUR Full Compliance Status
Pro-active compliance (Product out of EU RoHS legal scope)
China ROHS In Scope
Yes
With Recycled Cardboard
Yes
Return Indicator
Y
Function Option Id
ADVANCED
Market Segmentation Id
INDUSTRIAL
1 Phase Low Current Possible
false
Application In Domestic And Commercial Area Permitted
false
Base Load Current At High Overload
31.7 A
Braking To Standstill
by DC injection
Design Of Frequency Changer
U converter
Exchange Mode
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Isolation
between power and control terminals
Maximum Associated Fuse Rating
63.0 A
Method Of Access
slave Modbus TCP
Network Frequency
50-60 Hz
Operating Element Present
true
Optical Interface Present
false
Package Weight Lbs
25 kg
Power Loss Per Device Current Dependent
616.0 W
Product Availability
Non-Stock - Not normally stocked in distribution facility
Product Specific Application
process for industrial
Range Of Product
Altivar Process ATV900
Regulation Loop
adjustable PID regulator
Relative Symmetric Network Frequency Tolerance
5 %
Supporting Protocol For As Interface Safety At Work
false
Supporting Protocol For Bacnet
false
Supporting Protocol For Data Highway
false
Supporting Protocol For Devicenet Safety
false
Supporting Protocol For Foundation Fieldbus
false
Supporting Protocol For Knx
false
Supporting Protocol For Modbus
true
Supporting Protocol For Profibus
true
Supporting Protocol For Profinet Io
true
Supporting Protocol For Safetybus P
false
Supporting Protocol For Suconet
false
Sustainable Packaging
No
Transmission Frame
RTU
With Safety Function Safe Programmable Logic
false
Maximum Acceleration Under Shock Impact During Operation2
150 m/s² at 11 ms
Maximum Acceleration Under Shock Load During Transport2
150 m/s² at 11 ms
Maximum Acceleration Under Vibratory Load During Storage2
10 m/s² at 13...200 Hz
Maximum Deflection Under Vibratory Load During Operation2
1.5 mm at 2...13 Hz
Maximum Deflection Under Vibratory Load During Transport2
1.5 mm at 2...13 Hz
Permitted Relative Humidity During Storage2
class 1K5 according to EN 60721-3
With Safety Function Safe Brake Management Sbc Sbt2
true
With Safety Function Safe Operating Stop Sos2
false
With Safety Function Safe Speed Monitor Ssm2
false
With Safety Function Safe Torque Off Sto2
true
With Safety Function Safely Limited Speed Sls2
true
Application In Industrial Area Permitted
true
Medium Desc
variable speed drive, Altivar Process ATV900, ATV950, 18.5kW, 25hp, 380 to 480V, IP55, UL type12, disconnect switch
Product Kit Identifier
N
Maximum Acceleration Under Shock Impact During Operation3
150 m/s² at 11 ms
Maximum Acceleration Under Shock Load During Transport3
150 m/s² at 11 ms
Maximum Acceleration Under Vibratory Load During Storage3
10 m/s² at 13...200 Hz
Maximum Deflection Under Vibratory Load During Operation3
1.5 mm at 2...13 Hz
Maximum Deflection Under Vibratory Load During Transport3
1.5 mm at 2...13 Hz
Permitted Relative Humidity During Storage3
class 1K5 according to EN 60721-3
With Safety Function Safe Brake Management Sbc Sbt3
true
With Safety Function Safe Operating Stop Sos3
false
With Safety Function Safe Speed Monitor Ssm3
false
With Safety Function Safely Limited Position Slp3
false
With Sft Fct Safe Stop 2 Ss4
false
Database Version
2016-11
Pcr Version
PCR-ed3-EN-2015 04 02
Data Source
extrapolated product
Functional Unit Unit
Unit
Energy Model Installation A5 2
Electricity Mix; AC; < 1kV; EU-27
Energy Model End Of Life C1 C4 2
Electricity Mix; AC; < 1kV; EU-27
Us Rated Supply Voltage5
380...480 V - 15...10 %
Persona Type IdsEU, OM, OM8, SI
Apparent Power24 kVA 480 V normal duty), 20.3 kVA 480 V heavy duty)
Connector Type2 RJ45, 1 RJ45
Electrical Connectioncontrol screw terminal 0.5...1.5 mm², line side screw terminal 10...16 mm², motor screw terminal 10...16 mm², DC bus screw terminal 10...16 mm²
EMC Filterintegrated, with EMC plate option
Line Current33.4 A 380 V normal duty), 27.7 A 380 V heavy duty), 28.9 A 480 V normal duty), 24.4 A 480 V heavy duty)
Motor Power KW18.5 kW normal duty, 15.0 kW heavy duty
Sampling Duration2 ms +/- 0.5 ms DI1...DI8) - discrete input, 5 ms +/- 1 ms DI7, DI8) - pulse input, 1 ms +/- 1 ms AI1, AI2, AI3) - analog input, 5 ms +/- 1 ms AQ1, AQ2) - analog output
Synchronous Motor Control Profilepermanent magnet motor, synchronous reluctance motor
Type Of Polarizationno impedance, no impedance Modbus serial
Us Rated Supply Voltage2380...480 V, 380...480 V - 15...10 %
Environmental Class During Storage2class 1C3 according to EN 60721-3-1, class 1S2 according to EN 60721-3-1
Carbon Footprint Of The Distribution Phase A44.109318542, 4 kg CO2 eq.
Carbon Footprint Of The Installation Phase A57 kg CO2 eq., 7.4109270998
Carbon Footprint Of The Use Phase B2 B3 B4 B618 111 kg CO2 eq., 18111.4681307913
Environmental Class During Storage3class 1C3 according to EN 60721-3-1, class 1S2 according to EN 60721-3-1
Ue Rated Operational Voltage5380...480 V 18.5 kW normal duty, 380...480 V 15.0 kW heavy duty
Local Publishable Date2026-01-12
ServiceabilityYes
Field Service DivisionIDIBS
Legacy WEEE ScopeIn
EOLI Availability DisplayYes
Reach Full Compliance StatusReference contains Substances of Very High Concern above the threshold
Reach Compliance DirectiveReference contains Substances of Very High Concern above the threshold
ROHS EUR StatusCompliant with Exemptions
ROHS EUR Full Compliance Status IdPRO_ACTIVE_COMPLIANCE
Green Premium Status For ReportingGreen Premium product
Without Single Use PlasticNo
Dangerous Goods CodeLITHIUM METAL BATTERIES IN EQUIP. BUTTON CELL-BAT EXEMPT
Function OptionAdvanced
Market SegmentationIndustrial
4 Quadrant Operation Possibletrue
Assembly Styleenclosed
Base Load Current At Low Overload39.2 A
Computer Porttrue
Device ApplicationIndustrial Application
Housing Materialplastic
MarkingCE
Maximum Input Current Per Phase33.4 A
Mounting Modewall mount
Nominal Switching Frequency4 kHz
Operating Positionvertical +/- 10 degree
Overvoltage CategoryIII
Phase3 phase
Power Loss Static Current Independent23.0 W
Product Or Component Typevariable speed drive
Prospective Line Isc50 kA
Refresh Timerelay output R1, R2, R3)5 ms +/- 0.5 ms)
Relative Symmetric Mains Voltage Tolerance10 %
ReturnabilityYes
Supporting Protocol For Asifalse
Supporting Protocol For Cantrue
Supporting Protocol For Devicenetfalse
Supporting Protocol For Ethernet Iptrue
Supporting Protocol For Interbusfalse
Supporting Protocol For Lonfalse
Supporting Protocol For Other Bus Systemsfalse
Supporting Protocol For Profinet Cbatrue
Supporting Protocol For Profisafefalse
Supporting Protocol For Sercosfalse
Supporting Protocol For TCP IPtrue
Total Lifecycle Carbon Footprint18 351 kg CO2 eq.
Weee LabelThe product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Emc Limit Value Complied2true
Maximum Acceleration Under Shock Load During Storage2150 m/s² at 11 ms
Maximum Acceleration Under Vibrational Stress During Operation210 m/s² at 13...200 Hz
Maximum Acceleration Under Vibratory Load During Transport210 m/s² at 13...200 Hz
Maximum Deflection Under Vibratory Load During Storage21.5 mm at 2...13 Hz
Permitted Relative Humidity During Operation2class 3K5 according to EN 60721-3
Permitted Relative Humidity During Transport2class 2K5 according to EN 60721-3
With Safety Function Safe Direction Sdi2false
With Safety Function Safe Position Sp2false
With Safety Function Safe Stop 1 SS1true
With Safety Function Safely Limited Position Slp2false
With Sft Fct Safe Stop 2 Ssfalse
Supporting Protocol For Interbus Safetyfalse
Stocking FlagY
Emc Limit Value Complied3true
Maximum Acceleration Under Shock Load During Storage3150 m/s² at 11 ms
Maximum Acceleration Under Vibrational Stress During Operation310 m/s² at 13...200 Hz
Maximum Acceleration Under Vibratory Load During Transport310 m/s² at 13...200 Hz
Maximum Deflection Under Vibratory Load During Storage31.5 mm at 2...13 Hz
Permitted Relative Humidity During Operation3class 3K5 according to EN 60721-3
Permitted Relative Humidity During Transport3class 2K5 according to EN 60721-3
With Safety Function Safe Direction Sdi3false
With Safety Function Safe Position Sp3false
With Safety Function Safe Torque Off Sto3true
With Safety Function Safely Limited Speed Sls3true
Pep CodeENVPEP1406001EN
Pep Verification Date2021-11-01
Type Of Verification For The PepIndependent external review
Functional Unit DescriptionTo adapt the speed and torque of synchronous, asynchronous or reluctance motor to the machine s operating point for 22 kW electric motors for fluid management and industrial applications in IP55/UL type 1 conditions, at 380V to 480V rated 3-phase voltage supply, with disconnect switch. Calculation of the environmental impacts is based on 10 years of product service lifetime. The usage profile taken into account is 80% uptime in use phase at 75% loading rate and 20% uptime in stand by phase.
Energy Model Manufacturing A1 A3 2Energy model used: China
Energy Model Use B6 2Electricity Mix; AC; < 1kV; EU-27
Global Commercial StatusCommercialised
With Safety Function Safe Stop 1 Ss1 5true
Environment Attributes Main
Take Back
Nej, No
Ambient Air Transport Temperature
-40-70 °C, -40-70 °C
Operating Altitude
<= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, <= 3280.84 ft (1000 m) without derating, 1000...4800 m with current derating 1 % per 100 m
Recycled Metal Content At Cr Level
0 %
Mercury Free
Yes
Ambient Air Temperature For Storage
-40-70 °C
Environmental Disclosure
ENVPEP1406001EN
Packaging Made With Recycled Cardboard
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Pep Verification Date
2021-11-01
Type Of Verification For The Pep
Independent external review
Ambient Air Temperature For Operation-15-40 °C (without derating), -15-40 °C (without derating), -15-50 °C, -15-40 °C (without derating), -15-40 °C (without derating), 40-50 °C (with derating factor)
EU ROHS DirectiveCompliant By Exemption , Pro-active compliance (Product out of EU RoHS legal scope)
ROHS Exemption InformationYes
China ROHS RegulationX
Carbon Footprint18351.2795016313
Circularity ProfileENVEOLI1406001EN
IP Degree Of ProtectionIP55
Packaging Without Single Use PlasticNo
Pep CodeENVPEP1406001EN
Pcr VersionPCR-ed3-EN-2015 04 02
General Attributes
Phase
3 phase
Range Of Product
Altivar Process ATV900
Product Or Component Typevariable speed drive
Output Attributes
Analogue Output Type
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits, software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Discrete Output Type
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA, programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA, logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Analogue Output Number
2
Maximum Output Frequency
599 Hz
Nominal Output Current
39.2 A
Relay Output Number
3
Continuous Output Current39.2 A 4 kHz normal duty, 31.7 A 4 kHz heavy duty
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits, AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits