Description
The Easergy P5 is Schneider Electric's withdrawable protective relay for demanding medium voltage distribution applications. This motor relay offers withdrawable design with backup memory function enabling industry-leading 10 minute recovery time. It provides redundant Ethernet including IEC 61850 as well as plug and play communication modules that can evolve with your application. Easergy P5 offers safety, security, and connectivity built on more than 100 years of experience in protection relays. The Easergy P5 protection relay can be applied to all types of MV distribution networks. It can be supplied with 24 to 48 VDC. It works with low power instrument transformers. 3 LPCT inputs, 1 Schneider Electric specific CSH neutral current input and 4 LPVT inputs. It offers 31 digital inputs, 15 digital outputs and 3 arc sensors. It includes backup memory module. Communication modules can be added any time. The product dimensions are 180 mm in height (7.09 in), 152,4 mm in width (6.00 in) and 224 mm in depth 8.82 in) for a net weight of 3.5 kg (7.7 lbs). Easergy P5 is compliant with EN 60255-26, EN 60255-27 standards and with UL Standard. It provides Marine certification. This product can be flush mounted on the panel or in the rack. Flush mounting frames to ensure IP54 are available. Fixing and wiring accessories are included. Plug & play communication modules: Ethernet RSTP RJ45 (REL51038), Ethernet RSTP FO (REL51039), Ethernet HSR/PRP FO (REL51033). And also 2nd Ethernet RSTP RJ45 (REL51042), RS485 serial RJ45 (REL51036), RS485 serial FO (REL51040), Extension/backup memory (REL51034). IP54 flush mounting frame (REL51052), CSH core-balance CTs (59635, 59636, 59637), 8 temperature sensor module (59641), IRIG-B module (REL51045). Connection cords (59660, 59661, 59662), LPVT hub (EMS59573), VT adapter (EMS59572), arc flash sensors (from REL52801 to REL52810). eSetup Easergy Pro software with virtual injection testing and EcoStruxure Power Device app for simpler and safer operation and maintenance.
Specifications
Environment
Mechanical Robustness
vibrations class 2) IEC 60255-21-1 || shocks class 2) IEC 60255-21-2 || earthquakes class 2) IEC 60255-21-3 || vibrations GOST 17516.1
Environmental Characteristic
exposure to cold IEC 60068-2-1 || exposure to dry heat IEC 60068-2-2 || exposure to damp heat in service IEC 60068-2-78 || exposure to damp heat in service IEC 60068-2-30 || temperature variation IEC 60068-2-14 || salt mist IEC 60068-2-52 || influence of corrosion/gas test 2 IEC 60068-2-60 || influence of corrosion/gas test 4 IEC 60068-2-60 || stationary use at weatherprotected locations IEC 60721-3-3
Relative Humidity
0-93 % at 40-40 °C, without condensation, 56 days || 93-95 % at 25-55 °C, 6 cycles, 12 + 12 hours
Operating Altitude
2000 m
Ambient Air Temperature For Operation-40-85 °C 16 h ) || -40-70 °C 96 h )
switchgear control and monitoring || programmable switchgear interlocking || local/remote control || advanced logic engine
Integrated Connection Type
front USB 2.0 type A 2 || rear extension port 1 with backup memory
Arc Flash Protection
yes
Device Short Name
P5M30-CEDE-IAAAH-AADK
Input Type3 LPCT current || 1 CSH residual current || 4 voltage voltage || 31 digital
Connections - Terminalspin (input) || pin (output) || ring lugs (current transformer) || ring lugs (voltage transformer)
Device Mountingflush
Mounting Supportrack
Relay Applicationmotor
Product Or Component Typeprotection relay
Mounting Case Size30TE
Mounting Modewithdrawable
Setting4
Cybersecurityport hardening || firmware signature || client IP address filter || secured communication with assciated tools || role-based access control || security policy management || security log || IEC 62442-4-2 SL1
Type Of Measurementcurrent 3-phase || current zero sequence || current positive sequence || current negative sequence || current ratio of negative and positive || current phasor diagram view || current 2nd, 15th harmonics with THD || voltage 3-phase || voltage residual || voltage zero sequence || voltage positive sequence || voltage negative sequence || voltage phasor diagram view || frequency
[Us] Rated Supply Voltage24...48 V DC