Lead times may vary. For an accurate estimate please contact us.
Loading dialog...
Looking to buy a large quantity?
To view product inventory
Description
The Square D PowerPact™L-frame circuit breaker is designed to protect electrical systems from damage caused by overloads and short circuits for distribution systems supplied by transformers and distribution systems supplied by engine generator sets. This 3 poles, 400A, 600 VAC i-line circuit breaker with breaking capacity of 25 kA equipped with Micrologic 3.2 standard trip unit which offers adjustable protection settings for greater system flexibility type as well as communication capability. This L-Frame Mission Critical circuit breaker delivers high levels of selective coordination in a flexible design that can be easily configured for a variety of applications. Tested to be selectively coordinated with the QO™ family of miniature circuit breakers and the ED, EG, and EJ circuit breakers, this solution provides peace of mind when power availability is critical. Using Micrologic trip unit sensors and intelligence, PowerPact L-frame circuit breaker provides access to measurements of all the main electrical parameters on the built-in screen, on a dedicated front display module (FDM121) or through the communication. Through direct access to in-depth information and networking using open protocols, PowerPact L-frame circuit breaker with Micrologic trip unit lets operators optimize the management of electrical installations. Far more than just a circuit breaker, this device is a measurement and communication tool ready to meet energy-efficiency needs through optimized power requirements, increased energy availability, and improved installation management. The PowerPact L-frame circuit breaker is compliant with international standards IEC 60947-2 and UL 508/CSA 22.2 N°14, with UL 489.
Specifications
Rated Current
400 A
Rated Service Breaking Capacity
65 kA 220/240 V AC, 35 kA 380/440/415 V AC, 18 kA 500/525 V AC, 20 kA 250 V DC, 20 kA 500 V DC
Rated Insulation Voltage
750 V IEC 60947-2
Trip Unit Technology
Electronic, MicroLogic 3.3
Number of Poles
3P
Mounting Mode
I-Line bracket
Tightening Torque
50 N.m for AWG 2/0...500 kcmil
Wire Gauge
2 x AWG 2/0...500 kcmil aluminum/copper
Wire Stripping Length
31 mm, 61 mm
Width
140 mm (5.51 in)
Net Weight
6.2 kg (13.67 lb)
Communication Interface
Modbus, Ethernet
Certifications
UL, CSA, NOM
Pollution Degree
3 IEC 60947-1
Ambient Air Temperature for Operation
-25 to 70 °C (-13 to 158 °F)
Material
Not explicitly stated
Product Type
Circuit breaker
Electrical Connection
I-Line connection, line & lugs, load
Network Frequency
50/60 Hz
Reach Regulation
Contains SVHC above threshold
China RoHS Regulation
Out of scope
Environmental Disclosure
ENVPEP2206029EN
Mercury Free
Yes
Long Time Pick-Up Adjustment Range
0.25...1 x In
Warranty
18 months
Terminal Identifier
AL600LS52K3
Poles Description
3P
Breaking Capacity100 kA 240 V AC, 65 kA 480 V AC, 25 kA 600 V AC, 20 kA 250 V DC